Conduit Fill Calculator
Calculate NEC-compliant conduit fill using Chapter 9 tables for EMT, PVC, and RMC.

Raceway inputs
How to use this conduit fill tool
- Select conduit type and trade size (EMT, PVC Sch 40, or RMC).
- Choose insulation type and AWG/kcmil size from NEC Chapter 9 Table 5.
- Enter the number of identical conductors in the same raceway.
- Review fill percentage against NEC Chapter 9 Table 1 limits (53% / 31% / 40%).
Disclaimer
This calculator is for planning only. Conduit fill rules depend on conductor type, nipples, and local amendments. A licensed electrician or engineer must verify compliance before installation.
Sources & references
Based on NFPA 70 (NEC) 2023 unless noted. Confirm the edition adopted locally.
Frequently asked questions
- Which NEC tables does this conduit fill calculator use?
- We use Chapter 9 Table 1 (allowable fill percentages), Table 4 (conduit areas), and Table 5 (conductor areas) aligned with the 2023 NEC.
- Can I mix different wire sizes in one conduit?
- Real installations often mix sizes; this tool models one wire size at a time. For mixed fills, calculate total conductor area manually or run separate checks per conductor group.
- Does this include nipple exceptions?
- No. Short conduit nipples (≤24 in.) have different rules in NEC 300.15(C). Treat this as a standard raceway fill check.